Product Description
Operation Theory
When Gas Detector is connected to a power source, the power indicating lamp will light up, and in a few moments it will be in monitoring mode. When a gas leak occurs and exceeds a predetermined standard, the detector will produce a loud and regular sound and the operation indicating lamp will flash for warning. The detector includes a signal transfer terminal to activate other devices at the same time. When the gas density falls below predetermined standard, the detector will automatically return to monitoring status.
Specifications
| Power Type |
Control Panel
|
Individual
(110~230VAC adaptor) |
| Power Source |
12/24V DC
|
12V DC
|
| Standby Current |
40~45mA
|
65~70mA
|
| Alarm Current |
70~80mA
|
90~100mA
|
| Charging Period |
About 35 seconds
|
|
| Alarm Sound |
85dB/M and above
|
|
| Sensitivity |
0.05 ~ 0.30%
|
|
| Detection Type |
Natural Gas & Propane Gas
|
|
| Ambient Temperature |
-10℃ ~ +55℃
|
|
| Dimensions |
70mm(W)x35mm(D)x120mm(H)
|
|
| Weight |
About 130g
|
|
Product Selections
| Model |
AHG982-12B
|
AHG982-12C
|
AHG982-24B
|
AHG982-24C
|
| Power Source (from panel) |
12V DC
|
12V DC
|
24V DC
|
24V DC
|
| Alarm Sound |
|
|
||
| Relay Output COM. N.O. N.C. |
|
|
|
|
| Adaptor 110~230VAC |
Optional
|
Optional
|
N/A
|
N/A
|





Reviews
There are no reviews yet.